UV Quartz Sleeve for DWS7 UV Disinfection Units

MPN
ATS6-211
SKU
255
In stock
0 Available At My Branch
4 Available At All US Supply Locations

Campbell / ATS Quartz Sleeve for DWS-7 / SE-7 UV Systems

Replacement quartz sleeve for the Campbell / Aqua Treatment Services (ATS) ultraviolet disinfection systems model DWS-7 and SE-7 (rated for 6-7 gpm). The quartz sleeve encloses the UV lamp, protecting it from water contact while enabling UV transmission to disinfect the flowing water.

  • Part number / model: ATS6-211 (often listed as “Quartz Sleeve for DWS/SE7”) :contentReference[oaicite:0]{index=0}
  • Compatible systems: Campbell / ATS DWS-7, SE-7, and related UV units in the DWS / SE line :contentReference[oaicite:1]{index=1}
  • Flow rating: Intended for use in systems handling up to 6–7 gallons per minute (gpm) :contentReference[oaicite:2]{index=2}
  • Dimensions:
    • Length: 378 mm (≈ 14.88 in) :contentReference[oaicite:3]{index=3}
    • Inside diameter: 22 mm :contentReference[oaicite:4]{index=4}
    • Outside diameter: 24.5 mm :contentReference[oaicite:5]{index=5}
  • Ends: Open on both ends (for lamp insertion and compression sealing) :contentReference[oaicite:6]{index=6}
  • Material: High-quality UV-grade fused quartz (optimized for UV transmission and thermal stability) :contentReference[oaicite:7]{index=7}
  • Function:
    • Isolates the UV lamp from direct water contact while allowing ultraviolet light (254 nm) to pass through for disinfection.
    • Helps maintain a consistent lamp operating temperature and protects against shorting / electrical issues. :contentReference[oaicite:8]{index=8}
  • Sealing / Mounting:
    • Uses compression end nuts and O-rings at each end for a watertight seal within the threaded chamber ends. :contentReference[oaicite:9]{index=9}
    • Quartz sleeve is installed through the stainless steel chamber and slightly protrudes beyond each end nipple before securing compression nuts. :contentReference[oaicite:10]{index=10}
  • Maintenance & Replacement:
    • Recommended cleaning frequency: once monthly in normal conditions (or as needed depending on water quality) :contentReference[oaicite:11]{index=11}
    • Replacement interval: typically change quartz sleeve when lamp is changed (annually) or every 24 months as needed based on wear / clouding / damage. :contentReference[oaicite:12]{index=12}
    • When removing, loosen compression nuts carefully (avoid overtightening or applying torque with tools to prevent fracture) :contentReference[oaicite:13]{index=13}
    • After removal, clean with mild soap / water; more aggressive cleaning (e.g. weak acid) may be used if mineral deposits are present, following safety procedures. :contentReference[oaicite:14]{index=14}
    • Replace O-rings each time the sleeve is removed / serviced to maintain seal integrity. :contentReference[oaicite:15]{index=15}
  • Operational Constraints & Notes:
    • Handle quartz sleeve with care — avoid touching surfaces with bare fingers (oil deposits degrade UV transmission). :contentReference[oaicite:16]{index=16}
    • Ensure water conditions (turbidity, hardness, minerals) do not degrade performance—excess deposits reduce UV transmissivity. :contentReference[oaicite:17]{index=17}
    • Ensure proper alignment, straight installation, and avoid stresses on the sleeve during chamber assembly. :contentReference[oaicite:18]{index=18}
    • Quartz sleeve must remain intact — any chips or cracks will impair UV performance or lead to failure.
  • Weight: ~ 0.01 lb (package listing) :contentReference[oaicite:19]{index=19}
  • Warranty: Usually 1-year manufacturer warranty on quartz sleeve parts, subject to proper handling and installation. :contentReference[oaicite:20]{index=20}

Technical & Performance Notes

  • The quartz sleeve must maintain high UV transparency at 254 nm to allow the UV lamp’s germicidal output to pass into the water stream effectively.
  • Any fouling, clouding, or scaling of the quartz surface will reduce UV dose delivered and can compromise disinfection performance.
  • When replacing, the quartz sleeve must align concentrically with the lamp and chamber to minimize eccentricity, which could cause nonuniform UV exposure or lamp stress.
  • Because the UV systems are rated for up to 7 gpm, the sleeve design supports adequate UV exposure time within that flow regime (i.e. optical path length and sleeve wall thickness are chosen accordingly).
  • Always follow manufacturer’s procedural steps for installation, leak testing, and UV lamp insertion to preserve system integrity and warranty.

Specifications

Specifications
Weight 0.010000
Length (inches) 8.88
Width (inches) 22
Height (inches) 8.88
Item Type UV Treatment System Parts
Brand Non-Specified Brand
Manufacturer Non Specified Manufacturer
MPN ATS6-211
Sub Type UV Quartz Sleeve
Domestic/Import Done
Item Returns This item can be returned