Honeywell R8184G4009 – Protectorelay® Primary Control for Oil Burners
The Honeywell R8184G4009 Protectorelay® is a line voltage primary safety control designed for use with oil-fired heating equipment. This unit functions as a burner primary control, providing switching and flame monitoring for systems with intermittent ignition and solenoid valves. It is engineered for single-stage oil burners with cad cell flame detection.
This control includes safety timing, manual reset on safety lockout, and LED lockout indication at the terminal block. It is commonly installed in forced warm air furnaces, boilers, and other hydronic heating applications requiring dependable flame safeguard and oil burner management.
Application Features
Primary Burner Control – Controls burner motor, ignition transformer, and solenoid valve during heat call
Flame Monitoring – Solid-state circuitry detects cadmium sulfide (cad cell) flame sensor signal for flame presence
Safety Shutdown – Locks out after failed ignition or flame loss; requires manual reset to restore operation
LED Diagnostic – Lockout indicator provides visual fault signal for easy troubleshooting
Reset Capability – Top-mounted manual reset button for reactivation following lockout event
Mounting Versatility – Fits standard 4” junction box or mounts directly to burner housing with provided screws
Technical Specifications
Control Type: Intermittent ignition primary control with flame sensing
Input Voltage: 120 VAC, 60 Hz
Full Load Amperage: 7.4 A @ 120V
Locked Rotor Amperage: 44.4 A @ 120V
Operating Temperature: -40°F to 130°F (-40°C to 54°C)
Safety Switch Timing: 45 seconds (max.) lockout
Dimensions: 4-3/8" H × 4-1/8" W × 2-1/2" D
Installation Guidelines
For best results, install in accordance with local codes and applicable safety standards. The R8184G4009 mounts on a 4" x 4" junction box or directly to the burner chassis. Wiring must follow burner manufacturer and control specifications. Ensure cad cell sensor is properly positioned for accurate flame detection. This product is intended for use by qualified technicians only.
Professional Considerations
Compatible with conventional oil primary applications using cad cell sensors
Manual reset ensures safety following flame loss or ignition failure
Flame failure shutdown minimizes risk of unburned fuel discharge
Reliable solid-state flame sensing reduces maintenance frequency
Summary
The Honeywell R8184G4009/U Protectorelay® offers dependable safety control for residential and light commercial oil-fired burners. Its proven design, safety lockout, and LED diagnostics make it a standard choice for field service professionals requiring reliable flame safeguard and burner operation.